HVAC#Toshiba#VRF#BACnet#HVAC#Air Conditioning

Toshiba VRF KNX Integration: BACnet Gateway and Individual Room Control

SmartMāja Engineering Team·2027-01-22·9 min read

Variable refrigerant flow (VRF) systems from Toshiba — specifically the SMMS-e series — are a common choice for medium to large commercial buildings where multiple zones require individual temperature control with high efficiency. Unlike split units that have proprietary IR or simple on/off interfaces, the SMMS-e system supports a centralised BACnet/IP gateway that exposes each indoor unit as a fully addressable BACnet device. Combined with a LOYTEC LGATE-952 KNX/BACnet bridge, this creates a clean per-room KNX control architecture that ETS6 engineers can commission without deep BACnet expertise.

Toshiba SMMS-e VRF and BACnet gateway overview

The Toshiba SMMS-e VRF system supports 1 to 30 indoor units per outdoor unit pair, with indoor unit types spanning cassettes, ducted, wall-mounted, and ceiling-suspended. Each indoor unit communicates with the outdoor unit via the Toshiba AB proprietary bus. The Toshiba TCB-PCNT30TLE BACnet gateway connects to the Toshiba central control network via a dedicated RS-485 bus port (maximum 30 indoor units per gateway). The gateway presents each indoor unit as an individual BACnet device on the BACnet/IP network (UDP port 47808). Each BACnet device exposes the following BACnet objects: Analog Output AO0 — setpoint temperature (°C, 16.0–30.0); Binary Output BO0 — on/off command; Multi-State Output MSO0 — operating mode (1=Cool, 2=Heat, 3=Fan Only, 4=Auto, 5=Dry); Analog Output AO1 — fan speed (0=Auto, 1=Low, 2=Medium, 3=High); Analog Input AI0 — room temperature sensor reading; Binary Input BI0 — unit fault status. Gateway IP configuration: static IP on BMS LAN, subnet must be routable to LOYTEC LGATE.

LOYTEC LGATE-952 KNX/BACnet bridge configuration

The LOYTEC LGATE-952 acts as a BACnet client and KNX master simultaneously. Configuration via L-STUDIO software: create a BACnet/IP network connection (gateway IP, port 47808) → scan for BACnet devices → all TCB-PCNT30TLE registered indoor units appear as device list. For each indoor unit, bind BACnet objects to KNX data points: AO0 (setpoint) → KNX send group address with DPT 9.001; AI0 (room temp) → KNX send GA DPT 9.001; BO0 (on/off) → KNX send/receive GA DPT 1.001; MSO0 (mode) → KNX send/receive GA DPT 20.105 (HVAC mode: 0=Auto, 1=Comfort, 2=Standby, 3=Economy, 4=Protection — map to Toshiba modes accordingly); AO1 (fan speed) → KNX send/receive GA DPT 5.001.

Per-room KNX group address scheme

For a 12-room office building with 12 Toshiba indoor units, the KNX GA scheme follows a per-room structure under main group 9: GA 9/[room]/0 — On/Off DPT 1.001. GA 9/[room]/1 — Setpoint (°C) DPT 9.001. GA 9/[room]/2 — Actual room temperature DPT 9.001 (read from AI0). GA 9/[room]/3 — Operating mode DPT 20.105. GA 9/[room]/4 — Fan speed DPT 5.001. GA 9/[room]/5 — Fault status DPT 1.005. Where [room] = 1 through 12. This scheme allows individual room thermostats (e.g., MDT SCN-RT4.01 or Gira room controller) to directly address each VRF unit without intermediate logic. The LOYTEC LGATE handles all BACnet-to-KNX translation transparently.

Occupancy setback and group control

A PIR occupancy sensor (KNX, e.g., Jung 3360 WW) sends DPT 1.001 to GA 9/[room]/6 (occupancy). A KNX logic block implements setback: when occupancy = 0 (unoccupied) and HVAC mode is Comfort heating, setpoint GA 9/[room]/1 receives (current setpoint − 3°C); when mode is Comfort cooling, setpoint receives (current setpoint + 3°C). When room re-occupies, setpoint returns to scheduled comfort value. For group control of open-plan areas with multiple units, a KNX scene or group address fan-out sends identical setpoint/mode writes to all units in the zone simultaneously. VRF total power consumption monitoring: the Toshiba SMMS-e outdoor unit exposes a BACnet Analog Input for total system power (kW) — map this to GA 9/0/0 DPT 9.024 (kW) for energy dashboard display. Commissioning: verify each room by writing setpoint and confirming BACnet AI0 temperature reading stabilises; check fault bit BI0 with forced fault simulation if test mode available in service menu.

Need help with your KNX or DALI project?

Our certified engineers can discuss panel design, commissioning, integrations and project-specific edge cases. Free initial consultation.

Contact our engineers →
Ielādējas...
Uz augšu