Integration#HDL#Hotel#DALI#DND#Room Automation

HDL Automation KNX Hotel Room: DND/MUR Panel, DALI and Card Reader Integration

SmartMāja Engineering Team·2026-11-27·8 min read

HDL Automation KNX products are widely deployed in hotel room automation across the Middle East and increasingly in East European and Southeast Asian markets — offering ETS6-certified KNX devices at 30–50% lower cost than European brands. The HDL KNX hotel room solution combines a DND/MUR (Do Not Disturb / Make Up Room) panel, KNX card reader, DALI gateway, and touchpanel — all programmable in ETS6. This guide covers hardware configuration, KNX group address structure, HVAC setpoint scenes, and commissioning procedure for a standard hotel room.

HDL hotel room KNX hardware set

Standard HDL KNX hotel room BOM: (1) HDL KNX card reader (PoE or 24V DC, RFID 13.56MHz Mifare, KNX binary output on card insertion/removal). (2) HDL DND/MUR panel (2-button panel mounted outside room door: red LED = DND, green = MUR, each button sends KNX DPT 1.001 telegram on press). (3) HDL KNX DALI gateway (64 DALI devices, ETS6 plug-in commissioning). (4) HDL 5-inch TFT KNX touchpanel (wall-mount, KNX TP, shows room temperature, setpoint adjustment, scene buttons). (5) Compatible KNX thermostat/actuator: MDT SCN-HCA.02 or Zennio Z41 Pro (for HVAC setpoint display). (6) KNX power supply: MDT SCN-PS064.01 (640mA, DIN-rail). All HDL KNX devices: individual address via ETS6 programming button, standard KNX TP connection.

Card reader occupancy logic

HDL KNX card reader group objects: (1) Card status (DPT 1.001): 1 = card inserted, 0 = card removed. GA: 10/room_no/0. (2) Card type (DPT 5.010): 1 = guest card, 2 = housekeeping card, 3 = manager card (programmed in reader parameters). ETS6 logic using MDT Logic Module: Card inserted (GA 10/room_no/0 = 1) → HVAC setpoint = 21°C comfort (GA 7/room_no/2), Lighting scene = Scene 1 "Welcome" (GA 1/room_no/5 = 1). Card removed (GA 10/room_no/0 = 0, delayed 5 minutes) → HVAC setpoint = 26°C economy, Lighting scene = Scene 0 "Off". 5-minute delay prevents HVAC setback when guest briefly leaves room. Housekeeping card type (GA 10/room_no/1 = 2) → HVAC stays at 22°C (cleaning mode), Lighting scene = Scene 4 "Cleaning" (100% all lights).

DND/MUR panel KNX integration

HDL DND/MUR panel group objects: (1) DND button pressed (DPT 1.001, 1 on press). GA: 10/room_no/2. (2) MUR button pressed (DPT 1.001, 1 on press). GA: 10/room_no/3. (3) DND LED control (DPT 1.001, write, 1=red LED on). GA: 10/room_no/4. (4) MUR LED control (DPT 1.001, write, 1=green LED on). GA: 10/room_no/5. Logic: DND press → set DND flag GA 10/room_no/6 = 1 (toggle) → DND LED on. MUR press → set MUR flag GA 10/room_no/7 = 1 → MUR LED on → simultaneously clear DND flag. Corridor panel display: hotel management system (PMS) reads DND/MUR KNX GAs via ARISTO REST API or KNXnet/IP → shows housekeeping dashboard (which rooms are DND/MUR). Fermax video intercom integration: DND flag GA 10/room_no/6 = 1 → Comelit 1456B or Fermax 1490 service input = 1 → suppresses intercom bell during DND.

DALI lighting scenes for hotel room

HDL DALI gateway ETS6 plug-in: scan DALI bus → assign short addresses → create groups: Group 0 = All Room DALI, Group 1 = Ceiling (main), Group 2 = Bedside reading, Group 3 = Bathroom. Scene programming: Scene 1 "Welcome" = Group 0 at 60%, warm 2700K (DT8 driver). Scene 2 "Relax" = Group 1 at 20%, Group 2 at 80%, 2700K. Scene 3 "Presentation" (meeting room mode) = Group 0 at 90%, 4000K. Scene 4 "Cleaning" = Group 0 at 100%, 4000K. Scene 5 "Good Morning" = Group 1 at 30% (gentle wake-up). Scene 0 = Off. KNX GA for scene recall: GA 1/room_no/5 (DPT 18.001, HDL DALI gateway scene object). Scene trigger: card inserted → send Scene 1 to GA 1/room_no/5. Card removed + 5min → send Scene 0. DND button → send Scene 2 "Relax". Good night push-button → send Scene 0 (all off) + HVAC setpoint 22°C (sleep mode).

HVAC integration and setpoint scenes

HVAC control: fan coil unit (FCU) controlled via Zennio KLIC-DD or MDT heating actuator. KNX group objects for HVAC: On/Off (GA 7/room_no/0), Mode (GA 7/room_no/1, DPT 20.105), Setpoint (GA 7/room_no/2, DPT 9.001), Room temperature (GA 7/room_no/3, read-only). HDL touchpanel displays room temperature (from GA 7/room_no/3) and setpoint (GA 7/room_no/2 — guest can adjust ±3°C from comfort setpoint via touchpanel). Setpoint limits enforced in ETS6 (MDT Logic Module): min 18°C (comfort − 3°C), max 26°C (comfort + 5°C) — prevents guests setting extreme temperatures. KNX scenes for HVAC setpoints: card inserted → setpoint 21°C, card removed → setpoint 26°C, DND press → setpoint unchanged (maintain comfort during DND).

Project scale and cost comparison

Typical Middle East 200-room hotel: 200 rooms × HDL KNX hotel room set ≈ €450/room (card reader + DND panel + DALI gateway + touchpanel + cables) vs. European brand equivalent (Gira + MDT + Helvar) ≈ €900/room. Total saving: €90,000 for 200 rooms. Both achieve identical ETS6 programming and KNX functionality — HDL uses same KNX Association certified protocol. Risk: HDL product support and firmware updates less established than European brands — specify 10-year spare parts availability in contract. Recommendation: use European brands (MDT, Gira) for KNX actuators and logic modules (reliable, well-documented), HDL for hotel-specific hardware (DND panel, DALI gateway, card reader) where cost saving is largest.

Need help with your KNX or DALI project?

Our certified engineers can discuss panel design, commissioning, integrations and project-specific edge cases. Free initial consultation.

Contact our engineers →