HVAC#Floor Heating#KNX#HVAC

Danfoss TWA-A 24V Actuator: KNX Floor Heating Zone Wiring and ETS6 Setup

SmartMāja Engineering Team·2026-06-12·7 min read

The Danfoss TWA-A (Thermal Wax Actuator — Actuator) is the most widely installed floor heating zone valve actuator in European KNX installations. The TWA-A NC (normally closed) 24V version is the KNX standard: with 24V DC power removed, the valve closes — a fail-safe behaviour that stops heating if the KNX system loses power. Each TWA-A controls one zone circuit on a manifold (typically 8-12 manifold ports per heating circuit zone manifold). In a standard 6-zone underfloor heating system: 6× TWA-A 24V NC + one 8-channel KNX heating actuator module (MDT AKK-08.01 or ABB SA/M8.230.1) provides zone-by-zone KNX control.

TWA-A specification

Danfoss TWA-A NC 24V (article 088H3101): 24V AC/DC supply, normally closed (valve closes when power removed), IP21 rated, 3-wire connection (L, N, Earth), mounting: M30×1.5 threaded union on manifold valve body. Power consumption: 2.5W in operating phase (valve opening against wax actuator spring), 0.5W holding power when open. Opening time: 3 minutes from closed to fully open (thermal wax expansion). Closing time: 3 minutes from open to fully closed (spring return). Important: the 3-minute transition time must be accounted for in KNX PI controller timing — do not use pulse widths shorter than 5 minutes for TWA-A valves or they never fully open before closing again.

KNX heating actuator module wiring

MDT AKK-08.01 heating actuator (8 channels, 24V DC, DIN-rail, 4 modules wide): each channel = one relay contact switching 24V DC power to one TWA-A valve. Panel wiring: MDT AKK-08.01 terminal L+ (24V DC from PSU) → each TWA-A L terminal via separate cable. Neutral/negative from PSU → all TWA-A N terminals via neutral busbar. MDT AKK outputs switch the 24V DC positive — output contact in series between 24V bus and TWA-A terminal. Cable: 3-core 0.75mm² (or 2-core where earth not required for 24V SELV circuits). Run from panel to underfloor manifold location. Max distance: 30m at 0.75mm² for 2.5W load — voltage drop under 1V.

ETS6 configuration

In ETS6: add MDT AKK-08.01 to project topology. Per channel: heating mode = PWM (pulse-width modulation, 0-100%), PWM cycle time = 15 minutes (minimum for TWA-A thermal actuator — shorter cycle causes excessive valve cycling and reduced actuator life). Alternatively: PI control mode internal to AKK-08.01 (reads temperature sensor GA and room setpoint GA, calculates valve opening percentage). Group addresses: for each zone channel: GA_Valve_Zone1 (DPT 5.001, 0-100% valve opening), GA_Temp_Actual_Zone1 (DPT 9.001, actual room temperature from KNX room thermostat), GA_Setpoint_Zone1 (DPT 9.001, target room temperature). PI controller parameters: P-band 5K (temperature difference for full opening), I-time 180 minutes (integral time), dead band 0.3K (hysteresis).

Pump control integration

Uponor manifold with 6 zones: when all 6 TWA-A valves close, the circulation pump should stop to avoid pump cavitation and energy waste. MDT AKK-08.01 has a pump output contact (channel 9, normally open, closes when any zone valve is open). Wire pump output contact → 24V DC pump relay → Grundfos UPS circulation pump start/stop input. KNX GA: GA_Pump_Status (DPT 1.001, 1 = pump running) → connect to pump status binary input channel on MDT BE binary input module → monitoring via KNX room controller display.

Dew point protection for cooling

For KNX cooling mode with underfloor circuits (radiant cooling): dew point protection is critical — surface temperature must stay above room dew point to prevent condensation. Elsner P04-KNX-GPS provides outdoor humidity and temperature → calculates dew point and publishes DPT 9.001 GA. KNX function block: if surface temp (from floor sensor) < (dew point + 2°C) → close all cooling valves and send alarm GA. Floor sensor: PT1000 or NTC resistance thermometer wired to KNX analog input module (MDT AMS-0816.01) — compare floor temperature against dew point GA in ETS6 logic comparator block.

Need help with your KNX or DALI project?

Our certified engineers can discuss panel design, commissioning, integrations and project-specific edge cases. Free initial consultation.

Contact our engineers →
Ielādējas...
Uz augšu